This standard applies of tree wire and messenger supported spacer cable and CCX etc. These conductors are intended primarily for the distribution of electrical energy under normal conditions of overhead (aerial) installations. They are considered as covered conductors therefore the cables carry no voltage rating. The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer and tree wire.
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 15kV ACSR/XLPE/HDPE | |||||||
| 6 | 6/1 | 0.38 | 1.91 | 1.91 | 13.6 | 5.28 | 188 |
| 4 | 6/1 | 0.38 | 1.91 | 1.91 | 14.8 | 8.30 | 238 |
| 3 | 6/1 | 0.38 | 1.91 | 1.91 | 15.6 | 10.2 | 271 |
| 2 | 6/1 | 0.38 | 1.91 | 1.91 | 16.5 | 12.7 | 313 |
| 1 | 6/1 | 0.38 | 1.91 | 1.91 | 17.4 | 15.6 | 362 |
| 1/0 | 6/1 | 0.38 | 1.91 | 1.91 | 18.5 | 19.4 | 424 |
| 2/0 | 6/1 | 0.38 | 1.91 | 1.91 | 19.6 | 23.3 | 496 |
| 3/0 | 6/1 | 0.38 | 1.91 | 1.91 | 20.7 | 29.4 | 584 |
| 4/0 | 6/1 | 0.38 | 1.91 | 1.91 | 22.4 | 37.1 | 699 |
| 266.8 | 18/1 | 0.38 | 1.91 | 1.91 | 23.7 | 30.3 | 713 |
| 336.4 | 18/1 | 0.38 | 1.91 | 1.91 | 25.2 | 38.2 | 847 |
| Size ( kcmil) | Number of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 15kV AAAC/XLPE/HDPE | |||||||
| 48.69 | 7 | 0.38 | 1.91 | 1.91 | 15.2 | 7.83 | 223 |
| 77.47 | 7 | 0.38 | 1.91 | 1.91 | 16.8 | 12.4 | 286 |
| 123.3 | 7 | 0.38 | 1.91 | 1.91 | 19.0 | 18.9 | 383 |
| 155.4 | 7 | 0.38 | 1.91 | 1.91 | 20.1 | 23.8 | 443 |
| 195.7 | 7 | 0.38 | 1.91 | 1.91 | 21.5 | 30.0 | 521 |
| 246.9 | 7 | 0.38 | 1.91 | 1.91 | 23.0 | 37.8 | 614 |
| 312.8 | 19 | 0.38 | 1.91 | 1.91 | 24.9 | 46.5 | 740 |
| 394.5 | 19 | 0.38 | 1.91 | 1.91 | 27.4 | 58.6 | 892 |
| 465.4 | 19 | 0.38 | 1.91 | 1.91 | 28.4 | 69.2 | 1008 |
| 559.5 | 19 | 0.51 | 1.91 | 1.91 | 30.4 | 83.1 | 1168 |
| 652.4 | 19 | 0.51 | 1.91 | 1.91 | 31.8 | 97.0 | 1320 |
| 740.8 | 37 | 0.51 | 1.91 | 1.91 | 33.3 | 107 | 1463 |
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 15kV AAC/XLPE/HDPE | |||||||
| 4 | 7 | 0.38 | 1.91 | 1.91 | 14.4 | 3.52 | 204 |
| 2 | 7 | 0.38 | 1.91 | 1.91 | 15.8 | 5.39 | 259 |
| 1/0 | 7 | 0.38 | 1.91 | 1.91 | 17.7 | 7.96 | 341 |
| 2/0 | 7 | 0.38 | 1.91 | 1.91 | 18.6 | 9.99 | 394 |
| 3/0 | 7 | 0.38 | 1.91 | 1.91 | 19.7 | 12.15 | 459 |
| 4/0 | 7 | 0.38 | 1.91 | 1.91 | 21.1 | 15.30 | 541 |
| 266.8 | 19 | 0.38 | 1.91 | 1.91 | 23.0 | 19.89 | 648 |
| 336.4 | 19 | 0.38 | 1.91 | 1.91 | 24.9 | 24.57 | 775 |
| 397.5 | 19 | 0.38 | 1.91 | 1.91 | 26.1 | 28.44 | 878 |
| 477 | 19 | 0.38 | 1.91 | 1.91 | 27.9 | 33.30 | 1017 |
| 556.5 | 37 | 0.51 | 1.91 | 1.91 | 30.1 | 39.87 | 1161 |
| 636 | 37 | 0.51 | 1.91 | 1.91 | 31.5 | 45.36 | 1295 |
| 795 | 37 | 0.51 | 2.03 | 2.03 | 34.2 | 55.62 | 1557 |
25kV Tree Wire
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 25kV ACSR/XLPE/HDPE | |||||||
| 1/0 | 6/1 | 0.38 | 3.18 | 3.18 | 23.6 | 19.4 | 586 |
| 2/0 | 6/1 | 0.38 | 3.18 | 3.18 | 24.7 | 23.3 | 666 |
| 3/0 | 6/1 | 0.38 | 3.18 | 3.18 | 25.8 | 29.4 | 763 |
| 4/0 | 6/1 | 0.38 | 3.18 | 3.18 | 27.5 | 37.1 | 891 |
| 266.8 | 18/1 | 0.38 | 3.18 | 3.18 | 28.6 | 30.3 | 913 |
| 336.4 | 18/1 | 0.38 | 3.18 | 3.18 | 30.1 | 38.2 | 1058 |
| Size ( kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 25kV AAAC/XLPE/HDPE | |||||||
| 48.69 | 7 | 0.38 | 3.18 | 3.18 | 20.1 | 7.83 | 358 |
| 77.47 | 7 | 0.38 | 3.18 | 3.18 | 21.7 | 12.4 | 434 |
| 123.3 | 7 | 0.38 | 3.18 | 3.18 | 23.9 | 18.9 | 547 |
| 155.4 | 7 | 0.38 | 3.18 | 3.18 | 25.0 | 23.8 | 616 |
| 195.7 | 7 | 0.38 | 3.18 | 3.18 | 26.4 | 30.0 | 704 |
| 246.9 | 7 | 0.38 | 3.18 | 3.18 | 27.9 | 37.8 | 809 |
| 312.8 | 19 | 0.38 | 3.18 | 3.18 | 29.6 | 46.5 | 939 |
| 394.5 | 19 | 0.38 | 3.18 | 3.18 | 32.1 | 58.6 | 1109 |
| 465.4 | 19 | 0.38 | 3.18 | 3.18 | 33.1 | 69.2 | 1232 |
| 559.5 | 19 | 0.51 | 3.18 | 3.18 | 35.1 | 83.1 | 1407 |
| 652.4 | 19 | 0.51 | 3.18 | 3.18 | 36.5 | 97.0 | 1569 |
| 740.8 | 37 | 0.51 | 3.18 | 3.18 | 38.0 | 107 | 1723 |
| 927.2 | 37 | 0.51 | 3.18 | 3.18 | 40.9 | 135 | 2050 |
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 25kV AAC/XLPE/HDPE | |||||||
| 1/0 | 7 | 0.38 | 3.18 | 3.18 | 22.8 | 7.96 | 497 |
| 2/0 | 7 | 0.38 | 3.18 | 3.18 | 23.7 | 9.99 | 556 |
| 3/0 | 7 | 0.38 | 3.18 | 3.18 | 24.8 | 12.15 | 630 |
| 4/0 | 7 | 0.38 | 3.18 | 3.18 | 26.2 | 15.30 | 723 |
| 266.8 | 19 | 0.38 | 3.18 | 3.18 | 27.7 | 19.89 | 833 |
| 336.4 | 19 | 0.38 | 3.18 | 3.18 | 29.6 | 24.57 | 973 |
| 397.5 | 19 | 0.38 | 3.18 | 3.18 | 30.8 | 28.44 | 1086 |
| 477 | 19 | 0.38 | 3.18 | 3.18 | 32.6 | 33.30 | 1237 |
| 556.5 | 37 | 0.51 | 3.18 | 3.18 | 34.8 | 39.87 | 1398 |
| 636 | 37 | 0.51 | 3.18 | 3.18 | 36.2 | 45.36 | 1542 |
| 795 | 37 | 0.51 | 3.18 | 3.18 | 38.9 | 55.62 | 1824 |
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 35kV ACSR/XLPE/HDPE | |||||||
| 1/0 | 6/1 | 0.38 | 4.45 | 3.18 | 26.1 | 19.4 | 682 |
| 2/0 | 6/1 | 0.38 | 4.45 | 3.18 | 27.2 | 23.3 | 767 |
| 3/0 | 6/1 | 0.38 | 4.45 | 3.18 | 28.4 | 29.4 | 868 |
| 4/0 | 6/1 | 0.38 | 4.45 | 3.18 | 30.0 | 37.1 | 1002 |
| 266.8 | 18/1 | 0.38 | 4.45 | 3.18 | 31.1 | 30.3 | 1028 |
| 336.4 | 18/1 | 0.38 | 4.45 | 3.18 | 32.6 | 38.2 | 1179 |
| Size ( kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 35kV AAAC/XLPE/HDPE | |||||||
| 48.69 | 7 | 0.38 | 4.45 | 3.18 | 22.6 | 7.83 | 441 |
| 77.47 | 7 | 0.38 | 4.45 | 3.18 | 24.2 | 12.4 | 523 |
| 123.3 | 7 | 0.38 | 4.45 | 3.18 | 26.4 | 18.9 | 644 |
| 155.4 | 7 | 0.38 | 4.45 | 3.18 | 27.5 | 23.8 | 718 |
| 195.7 | 7 | 0.38 | 4.45 | 3.18 | 28.9 | 30.0 | 811 |
| 246.9 | 7 | 0.38 | 4.45 | 3.18 | 30.4 | 37.8 | 922 |
| 312.8 | 19 | 0.38 | 4.45 | 3.18 | 32.1 | 46.5 | 1059 |
| 394.5 | 19 | 0.38 | 4.45 | 3.18 | 34.6 | 58.6 | 1238 |
| 465.4 | 19 | 0.38 | 4.45 | 3.18 | 35.6 | 69.2 | 1365 |
| 559.5 | 19 | 0.51 | 4.45 | 3.18 | 37.6 | 83.1 | 1547 |
| 652.4 | 19 | 0.51 | 4.45 | 3.18 | 39.0 | 97.0 | 1715 |
| 740.8 | 37 | 0.51 | 4.45 | 3.18 | 40.5 | 107 | 1874 |
| 927.2 | 37 | 0.51 | 4.45 | 3.18 | 43.4 | 135 | 2213 |
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 35kV AAC/XLPE/HDPE | |||||||
| 1/0 | 7 | 0.38 | 4.45 | 3.18 | 25.3 | 7.96 | 590 |
| 2/0 | 7 | 0.38 | 4.45 | 3.18 | 26.2 | 9.99 | 653 |
| 3/0 | 7 | 0.38 | 4.45 | 3.18 | 27.3 | 12.15 | 731 |
| 4/0 | 7 | 0.38 | 4.45 | 3.18 | 28.7 | 15.30 | 829 |
| 266.8 | 19 | 0.38 | 4.45 | 3.18 | 30.2 | 19.89 | 946 |
| 336.4 | 19 | 0.38 | 4.45 | 3.18 | 32.1 | 24.57 | 1094 |
| 397.5 | 19 | 0.38 | 4.45 | 3.18 | 33.3 | 28.44 | 1210 |
| 477 | 19 | 0.38 | 4.45 | 3.18 | 35.1 | 33.30 | 1369 |
| 556.5 | 37 | 0.51 | 4.45 | 3.18 | 37.3 | 39.87 | 1538 |
| 636 | 37 | 0.51 | 4.45 | 3.18 | 38.8 | 45.36 | 1688 |
| 795 | 37 | 0.51 | 4.45 | 3.18 | 41.4 | 55.62 | 1980 |
46kV Tree Wire
| Size (kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 46kV AAAC/XLPE/HDPE | |||||||
| 48.69 | 7 | 0.38 | 5.72 | 4.45 | 27.7 | 7.83 | 640 |
| 77.47 | 7 | 0.38 | 5.72 | 4.45 | 29.3 | 12.4 | 734 |
| 123.3 | 7 | 0.38 | 5.72 | 4.45 | 31.5 | 18.9 | 873 |
| 155.4 | 7 | 0.38 | 5.72 | 4.45 | 32.6 | 23.8 | 955 |
| 195.7 | 7 | 0.38 | 5.72 | 4.45 | 34.0 | 30.0 | 1060 |
| 246.9 | 7 | 0.38 | 5.72 | 4.45 | 35.5 | 37.8 | 1182 |
| 312.8 | 19 | 0.38 | 5.72 | 4.45 | 37.2 | 46.5 | 1332 |
| 394.5 | 19 | 0.38 | 5.72 | 4.45 | 39.7 | 58.6 | 1531 |
| 465.4 | 19 | 0.38 | 5.72 | 4.45 | 40.7 | 69.2 | 1666 |
| 559.5 | 19 | 0.51 | 5.72 | 4.45 | 42.7 | 83.1 | 1864 |
| 652.4 | 19 | 0.51 | 5.72 | 4.45 | 44.1 | 97.0 | 2043 |
| 740.8 | 37 | 0.51 | 5.72 | 4.45 | 45.6 | 107 | 2214 |
| 927.2 | 37 | 0.51 | 5.72 | 4.45 | 48.5 | 135 | 2575 |
| Size (AWG or kcmil) | No. of Wires | Covering Thickness | Cable Diameter | Rated Strength | Weight | ||
| Conductor Shield | Inner Layer | Outer Layer | |||||
| No. | mm | mm | mm | mm | kN | kg/km | |
| 3-Layer 46kV AAC/XLPE/HDPE | |||||||
| 1/0 | 7 | 0.38 | 5.72 | 4.45 | 30.4 | 7.96 | 810 |
| 2/0 | 7 | 0.38 | 5.72 | 4.45 | 31.3 | 9.99 | 880 |
| 3/0 | 7 | 0.38 | 5.72 | 4.45 | 32.4 | 12.15 | 968 |
| 4/0 | 7 | 0.38 | 5.72 | 4.45 | 33.8 | 15.30 | 1077 |
| 266.8 | 19 | 0.38 | 5.72 | 4.45 | 35.3 | 19.89 | 1205 |
| 336.4 | 19 | 0.38 | 5.72 | 4.45 | 37.2 | 24.57 | 1367 |
| 397.5 | 19 | 0.38 | 5.72 | 4.45 | 38.4 | 28.44 | 1494 |
| 477 | 19 | 0.38 | 5.72 | 4.45 | 40.2 | 33.30 | 1666 |
| 556.5 | 37 | 0.51 | 5.72 | 4.45 | 42.4 | 39.87 | 1853 |
| 636 | 37 | 0.51 | 5.72 | 4.45 | 43.9 | 45.36 | 2014 |
| 795 | 37 | 0.51 | 5.72 | 4.45 | 46.5 | 55.62 | 2326 |