CU PVC PVC Control Cable
Voltage Rating: 300/500V
Conductor: soft annealed copper
Insulation: PVC
Sheath: PVC
Email:uvlead@aliyun.com
Email:tlfast@aliyun.com
YY Control Cable is used as a control cable on conveyors, assembly and production lines. It is generally used indoors as an interconnecting cable in signal and control equipment.
These cables are not UV resistant but can be used outdoors if adequately protected against direct sunlight in trunking etc.
Generally to BS6500 and VDE0250

Voltage Rating: 300/500 Volts
Temperature limits:
Static: -20°C to +80°C
Flexing: -5°C to +70°C
Minimum Bending Radius: As Per Manufacturers Datasheet
Should not be installed at temperatures below -5°C
| Part No. | No. Cores | Conduct or Cross Secton Area (mm²) | Cable Cross Secton Area (mm²) | Overall Diameter (mm) | Gland Size | Cleat Size | Nominal Weight (kg/km) | Resistance of Copper Conductor (Ω/Km) at 200C |
| 2C.75YY | 2 | 0.75 | 27.32 | 5.9 | 20S | 3 | 50 | 26 |
| 2C1.0YY | 2 | 1 | 30.17 | 6.2 | 20S | 3 | 55 | 19.5 |
| 2C1.5YY | 2 | 1.5 | 36.29 | 6.8 | 20S | 3 | 80 | 13.3 |
| 2C2.5YY | 2 | 2.5 | 55.38 | 8.4 | 20S | 3 | 135 | 7.98 |
| 2C4.0YY | 2 | 4 | 84.9 | 10.4 | 20S | 4 | 197 | 4.95 |
| 2C6.0YY | 2 | 6 | 113.04 | 12 | 20 | 5 | 225 | 3.3 |
| 2C10YY | 2 | 10 | 171.94 | 14.8 | 25 | 6 | 460 | 1.91 |
3 Core YY Control Cable Specifications
| Part No. | No. Cores | Conduct or Cross Secton Area (mm²) | Cable Cross Secton Area (mm²) | Overall Diameter (mm) | Gland Size | Cleat Size | Nominal Weight (kg/km) | Resistance of Copper Conductor (Ω/Km) at 200C |
| 3C.75YY | 3 | 0.75 | 30.17 | 6.2 | 20S | 3 | 60 | 26 |
| 3C1.0YY | 3 | 1 | 33.16 | 6.5 | 20S | 3 | 70 | 19.5 |
| 3C1.5YY | 3 | 1.5 | 40.69 | 7.2 | 20S | 3 | 95 | 13.3 |
| 3C2.5YY | 3 | 2.5 | 62.17 | 8.9 | 20S | 4 | 165 | 7.98 |
| 3C4.0YY | 3 | 4 | 98.47 | 11.2 | 20 | 5 | 250 | 4.95 |
| 3C6.0YY | 3 | 6 | 128.61 | 12.8 | 20 | 6 | 305 | 3.3 |
| 3C10YY | 3 | 10 | 195.96 | 15.8 | 25 | 7 | 590 | 1.91 |
| 3C16YY | 3 | 16 | 265.76 | 18.4 | 32 | 8 | 800 | 1.21 |
| 3C25YY | 3 | 25 | 633.14 | 28.4 | 40 | 12 | 1400 | 0.78 |
| 3C35YY | 3 | 35 | 798.82 | 31.9 | 40 | 14 | 1840 | 0.554 |
| 3C50YY | 3 | 50 | 1115.71 | 37.7 | 50 | 16 | 2550 | 0.38 |
4 Core YY Control Cable Specifications
| Part No. | No. Cores | Conduct or Cross Secton Area (mm²) | Cable Cross Secton Area (mm²) | Overall Diameter (mm) | Gland Size | Cleat Size | Nominal Weight (kg/km) | Resistance of Copper Conductor (Ω/Km) at 200C |
| 4C.75YY | 4 | 0.75 | 35.23 | 6.7 | 20S | 3 | 70 | 26 |
| 4C1.0YY | 4 | 1 | 39.57 | 7.1 | 20S | 3 | 85 | 19.5 |
| 4C1.5YY | 4 | 1.5 | 51.5 | 8.1 | 20S | 3 | 120 | 13.3 |
| 4C2.5YY | 4 | 2.5 | 73.86 | 9.7 | 20S | 4 | 200 | 7.98 |
| 4C4.0YY | 4 | 4 | 130.63 | 12.9 | 20 | 6 | 300 | 4.95 |
| 4C6.0YY | 4 | 6 | 160.52 | 14.3 | 25 | 6 | 390 | 3.3 |
| 4C10YY | 4 | 10 | 243.16 | 17.6 | 25 | 7 | 720 | 1.91 |
| 4C16YY | 4 | 16 | 329.89 | 20.5 | 32 | 9 | 1000 | 1.21 |
| 4C25YY | 4 | 25 | 778.91 | 31.5 | 40 | 14 | 1800 | 0.78 |
| 4C35YY | 4 | 35 | 978.18 | 35.3 | 50 | 14 | 2380 | 0.554 |
| 4C50YY | 4 | 50 | 1365.02 | 41.7 | 63 | 18 | 3290 | 0.386 |
5 Core YY Control Cable Specifications
| Part No. | No. Cores | Conduct or Cross Secton Area (mm²) | Cable Cross Secton Area (mm²) | Overall Diameter (mm) | Gland Size | Cleat Size | Nominal Weight (kg/km) | Resistance of Copper Conductor (Ω/Km) at 200C |
| 5C.75YY | 5 | 0.75 | 42.98 | 7.4 | 20S | 3 | 88.5 | 26 |
| 5C1.0YY | 5 | 1 | 46.54 | 7.7 | 20S | 3 | 100 | 19.5 |
| 5C1.5YY | 5 | 1.5 | 63.58 | 9 | 20S | 4 | 150 | 13.3 |
| 5C2.5YY | 5 | 2.5 | 91.56 | 10.8 | 20 | 5 | 255 | 7.98 |
| 5C4.0YY | 5 | 4 | 147.33 | 13.7 | 20 | 6 | 355 | 4.95 |
| 5C6.0YY | 5 | 6 | 191.03 | 15.6 | 25 | 7 | 470 | 3.3 |
| 5C10YY | 5 | 10 | 298.49 | 19.5 | 32 | 7 | 865 | 1.91 |
| 5C16YY | 5 | 16 | 404.5 | 22.7 | 40 | 9 | 1250 | 1.21 |
| 5C25YY | 5 | 25 | 945.21 | 34.7 | 50 | 14 | 2220 | 0.78 |
| 5C35YY | 5 | 35 | 1187.86 | 38.9 | 63 | 16 | 2790 | 0.554 |