Conductor: Circular compressed aluminum, aluminum-alloy, copper.
Conductor shield: Semi-conducting cross-linked polyethylene.
Insulation: Cross-linked polyethylene (Natural)
Sheath: PE & XLPE
Package : Export wooden drum & iron wooden drum or as customer require
Email:uvlead@aliyun.com
Email:tlfast@aliyun.com
Aerial Insulated Cables with voltages of 10kV.The products primarily used for the distribution of electrical energy under normal conditions of overhead (aerial) installations.The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer etc.
| Type | No. of Cores | Nominal size mm² |
| CU/XLPE,AAC/XLPE,AAAC/XLPE | 1 | 10 ~ 400 |
| 3 | 25 ~ 400 | |
| 3+k(A) or 3+k(B) | 25 ~ 400 ; k:25~120 | |
| CU/PE,AAC/PE,AAAC/PE,CU/XLPE,AAC/XLPE,AAAC/XLPE | 1 | 10 ~ 400 |
| AAC/XLPE,AAAC/XLPE | 3 | 25 ~ 400 |
| 3+k(A) or 3+k(B) | 25 ~ 400 ; k:25~120 | |
| The k is a load-bearing core. (A) means steel carrying stranded wire, (B) means aluminum alloy carrying stranded wire. | ||
10kV Aerial Insulated Cables
| Nominal Size | Min. No. of Wires | Approx. Diameter of Conductor | Min. Thickness of Conductor screen (Approx.) | Nominal Thickness of Insulation | Nominal Thickness of Insulation Screen | Min. Breaking Load | |||
| Reduced | Nominal | Hard Copper | Soft Copper | Hard Copper | |||||
| mm² | No. | mm | mm | mm | mm | Ω/km | Ω/km | N | |
| 10 | 6 | 3.8 | 0.5 | - | 3.4 | - | 1.830 | - | |
| 16 | 6 | 4.8 | 0.5 | - | 3.4 | - | 1.150 | - | |
| 25 | 6 | 6.0 | 0.5 | 2.5 | 3.4 | 0.749 | 0.727 | 8465 | |
| 35 | 6 | 7.0 | 0.5 | 2.5 | 3.4 | 0.540 | 0.524 | 11731 | |
| 50 | 6 | 8.3 | 0.5 | 2.5 | 3.4 | 0.399 | 0.387 | 16052 | |
| 70 | 12 | 10.0 | 0.5 | 2.5 | 3.4 | 0.276 | 0.268 | 23461 | |
| 95 | 15 | 11.6 | 0.6 | 2.5 | 3.4 | 0.199 | 0.193 | 31759 | |
| 120 | 18 | 13.0 | 0.6 | 2.5 | 3.4 | 0.158 | 0.153 | 39911 | |
| 150 | 18 | 14.6 | 0.6 | 2.5 | 3.4 | 0.128 | - | 49505 | |
| 185 | 30 | 16.2 | 0.6 | 2.5 | 3.4 | 0.1021 | - | 61846 | |
| 240 | 34 | 18.4 | 0.6 | 2.5 | 3.4 | 0.0777 | - | 79823 | |
| 300 | 34 | 20.6 | 0.6 | 2.5 | 3.4 | 0.0619 | - | 99788 | |
| 400 | 53 | 23.8 | 0.6 | 2.5 | 3.4 | 0.0484 | - | 133040 | |
10kV Aerial Insulated Cables
| Nominal Size | Min. No. of Wires | Approx. Diameter of Conductor | Min. Thickness of Conductor Screen (Approx.) | Nominal Thickness of Insulation | Nominal Thickness of Insulation Screen | Min. Breaking Load | ||||
| Reduced | Nominal | AAC | AAAC | AAC | AAAC | |||||
| mm² | No. | mm | mm | mm | mm | Ω/km | Ω/km | N | N | |
| 10 | 6 | 3.8 | 0.5 | - | 3.4 | 3.080 | 3.574 | - | - | |
| 16 | 6 | 4.8 | 0.5 | - | 3.4 | 1.910 | 2.217 | - | - | |
| 25 | 6 | 6.0 | 0.5 | 2.5 | 3.4 | 1.200 | 1.393 | 3762 | 6284 | |
| 35 | 6 | 7.0 | 0.5 | 2.5 | 3.4 | 0.868 | 1.007 | 5177 | 8800 | |
| 50 | 6 | 8.3 | 0.5 | 2.5 | 3.4 | 0.641 | 0.744 | 7011 | 12569 | |
| 70 | 12 | 10.0 | 0.5 | 2.5 | 3.4 | 0.443 | 0.514 | 10354 | 17596 | |
| 95 | 15 | 11.6 | 0.6 | 2.5 | 3.4 | 0.320 | 0.371 | 13727 | 23880 | |
| 120 | 18 | 13.0 | 0.6 | 2.5 | 3.4 | 0.253 | 0.294 | 17339 | 30164 | |
| 150 | 18 | 14.6 | 0.6 | 2.5 | 3.4 | 0.206 | 0.239 | 21033 | 37706 | |
| 185 | 30 | 16.2 | 0.6 | 2.5 | 3.4 | 0.164 | 0.190 | 26732 | 46503 | |
| 240 | 34 | 18.4 | 0.6 | 2.5 | 3.4 | 0.125 | 0.145 | 34679 | 60329 | |
| 300 | 34 | 20.6 | 0.6 | 2.5 | 3.4 | 0.100 | 0.116 | 43349 | 75411 | |
| 400 | 53 | 23.8 | 0.6 | 2.5 | 3.4 | 0.0778 | 0.0904 | 55707 | 100548 | |
22.9kV ACSR/AW-OC Aerial Insulated Cables
| Size (mm²) | No. and Dia. of Wires | Conductor Diameter | Insulation Thickness | Cable Diameter | Rated Strength | Weight | |
| AL | St | ||||||
| No. | No. /mm | mm | mm | mm | kgf | kg/km | |
| 22.9 kV ACSR/AW-OC/XLPE | |||||||
| 32 | 6/SB | 1/2.6 | 7.2 | 3.0 | 13.2 | 1090 | 210 |
| 58 | 6/SB | 1/3.5 | 9.7 | 3.0 | 15.7 | 1900 | 330 |
| 95 | 6/SB | 1/3.5 | 12.0 | 3.5 | 19.0 | 2360 | 530 |
| 160 | 18/SB | 1/3.2 | 15.4 | 4.0 | 23.4 | 3080 | 730 |
| 240 | 18/SB | 1/4.0 | 18.9 | 4.0 | 27.0 | 4500 | 1040 |