RVFAV-K Cable

Single Core Flexible Power Cable 0.6/1kV with Aluminum Tape Armoured

Cable Type: RVFAV-K

Conductor: Plain copper conductor, class 5

Insulation: Cross-linked polyethylene (XLPE)

Armoured: Aluminum Tape Armoured

Over sheath: Flexible PVC

Armour: Double steel or aluminium tape armour

Email:uvlead@aliyun.com

Email:tlfast@aliyun.com

RVFAV-K Cable Application

RVFAV-K cables are indicated for the transport and distribution of low voltage electricity. Their use is recommended for industrial connections, service connections, internal distribution and outdoor connections. They can be used in underground networks and permanent installations. The metal band provides greater protection against mechanical aggressions and the action of rodents.

Suitable for the following installations:
- Underground networks for low voltage distribution
- Outdoor lighting installations.Indoor or receiver installations
- Installations in premises with special characteristics

RVFAV-K Cable Standards

Reference Standards: UNE 21123, HD 603 S1 and IEC 60502


CONSTRUCTION :

RVFAV-K Cable Construction


RVFAV-K Cable

Conductor: Electrolytic annealed copper conductor, class 5 (flexible) according to EN 60228 and IEC 60228.
Insulation: Cross-linked polyethylene (XLPE) insulation type XLPE according to IEC 60502-1.
Insualtion Color: Natural
Armour bedding: Black extruded PVC separation sheath.
Armour: Double aluminium tape armour. Aluminium armour is used in single-core cables to avoid parasite currents that may overheat the cable. 
Outer sheath: Flexible PVC outer sheath, Black colour.


CHARACTERISTICS :

RVFAV-K Cable Characteristics 

Electrical performance: Low voltage 0,6/1kV.
Thermal performance:
Maximum service temperature: 90ºC.
Maximum short-circuit temperature: 250ºC (max. 5 s).
Minimum service temperature: -40ºC (fixed and protected installations).
Fire performance:
Flame non-propagation according to EN 60332-1 and IEC 60332-1.
Reduced halogen emission. Chlorine <15%.
Reaction to fire CPR: Eca, according to EN 50575.
Mechanical performance:
Minimum bending radius: x5 cable diameter.
Impact resistance: AG2 Medium severity.
Environmental performance
Chemical & Oil resistance: Good.
UV Resistant: UNE 211605.
Installation conditions
Open Air.
Buried.
In conduit.
 
Other

Meter by meter marking. 


PARAMETER :

RVFAV-K Cable Parameter

Cross sectionDiameterWeightOpen air 30ºCBuried 20ºCVoltage drop
(mm2)(mm)(kg/km)(A)(A)(V/A.km)
1x1614,4370101792,55
1x25164851351011,61
1x3517,15951691221,16
1x5018,67302071440,86
1x7020,39602681780,594
1x9522,412553282110,428
1x12024,415103832400,339
1x15026,318104442710,275
1x18528,322155103040,220
1x24031,328056073510,167
1x3003434207033960,133