NYY Cable Duplex
Conductor: Plain annealed copper
Insulation: PVC
Sheath: PVC
Voltage : 0.6/1kV
Number of cores: Duplex
Package Export wooden drum & iron wooden drum or as customer require
Email:uvlead@aliyun.com
Email:tlfast@aliyun.com
National : ICEA S-95-658; NTP-IEC 60228; NTP-IEC 60502-1; UL 2556
International :IEC 60228; IEC 60332-1-2; IEC 60502-1; IEC 60811-401; IEC 60811-402; IEC 60811-501; IEC 60811-504; IEC 60811-505; IEC 60811-506; IEC 60811-508; IEC 60811-509
1. Conductor: Compact soft copper, class 2.
2. Insulation: Compound polyvinyl chloride PVC
3. Outer sheath: Compound polyvinyl chloride PVC
4. Tape: Polyester tape.
Main characteristics:
Good electrical and mechanical properties. The PVC outer sheath provides an adequate resistance to grease, oils and abrasion. Resistance to sunlight. Flame retardant.
| Electrical Characteristics | |
| Rated Voltage Uo/U (Um) | 0.6/ 1 (1.2) kV |
| Dielectric strength | 3.5 kV |
| Time of application Dielectric strength core to screen AC | 5 min. |
| Usage Characteristics | |
| Flame retardant | IEC 60332-1-2; FT1 |
| Oil resistance | ICEA S-95-658 |
| U.V resistance | UL 2556 - Sunlight Resistance |
| Maximum operating temperature | 80 °C |
| Overload maximum core temperature | 100 °C |
| Short-circuit max. conductor temperature | 160 °C |
| Number of cores | Cross section mm2 | Minimum number of wires | Conductor diameter mm | Insulation thickness mm | Sheath thickness mm | Outside diameter mm | Nominal Weight kg/km |
| 2 | 6 | 7 | 3 | 1 | 0.9 | 13.9 | 285 |
| 2 | 16 | 7 | 4.6 | 1 | 0.9 | 17.2 | 597 |
| 2 | 25 | 7 | 5.9 | 1.2 | 0.9 | 20.5 | 625 |
| 2 | 35 | 7 | 6.9 | 1.1 | 0.9 | 22.6 | 829 |